huadong log
Loading...

P19 or P19/P21 RFOU 12/20KV Cables

Home/NEK 606 Offshore & Marine Cables/P19 or P19/P21 RFOU 12/20KV Cables

P19 or P19/P21 RFOU 12/20KV Cables Applications

P19 or P19/P21 RFOU 12/20KV Cables are flame retardant, low smoke, halogen-free and mud resistant, used for fixed installation for medium voltage power.

P19 or P19/P21 RFOU 12/20KV Cables Standards

IEC 60092-353 IEC 60092-351
IEC 60092-359 IEC 60332-1
IEC 60332-3-22 IEC 60754-1,2
IEC 61034-1,2 NEK 606:2004
P4 or P4/P11 RFOU/TFOU 8.7/15KV P4 or P4/P11 RFOU/TFOU 8.7/15KV

P19 or P19/P21 RFOU 12/20KV Cables Construction

  • Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
  • Conductor Screen : Semi conducting material.
  • Insulation : Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
  • Insulation Screen : Semi conducting material and tinned copper wire braid.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath : Halogen free thermosetting compound, SHF2 (for TYPE P19), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P19/P21),coloured red.

Optional

  • P20 or P20/P22 RFOU/TFOU 18/30(36) kV.

P19 or P19/P21 RFOU 12/20KV Cables Electrical Characteristics

Nominal Cross Section Area mm² 16 25 35 50 70 95
Nominal Conductor Diameter mm 5.2 6.5 7.4 8.7 10.3 12.2
Maximum DC Resistant@20℃ Ω/km 1.16 0.734 0.529 0.391 0.27 0.195
Continuous Current Rating@45℃1 Core A 96 127 157 196 242 293
Continuous Current Rating@45℃3 Core A 67 89 110 137 169 205
Short Circuit Current 1s A 2290 3580 5010 7150 10020 13590
Operating Voltage KV 12/20 12/20 12/20 12/20 12/20 12/20

 

Nominal Cross Section Area mm² 120 150 185 240 300
Nominal Conductor Diameter mm 13.8 15.1 17.0 19.6 21.9
Maximum DC Resistant@20℃ Ω/km 0.154 0.126 0.1 0.0762 0.0607
Continuous Current Rating@45℃1 Core A 339 389 444 522 601
Continuous Current Rating@45℃3 Core A 237 272 311 365 421
Short Circuit Current 1s A 17170 21460 26470 34340 42930
Operating Voltage KV 12/20 12/20 12/20 12/20 12/20

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties

  • Bending Radius :15×OD (during installation); 9×OD (fixed installed).
  • Temperature Range : -20℃ ~ +90℃.

P19 or P19/P21 RFOU 12/20KV Cables Dimensions and Weight

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Sheath Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
Inner Outer
1×16 5.5 1.4 1.2 28 1200
1×25 5.5 1.5 1.2 31.6 1530
1×35 5.5 1.8 1.3 32.3 1595
1×50 5.5 1.8 1.4 33.8 1795
1×70 5.5 1.9 1.4 34.6 2070
1×95 5.5 2.0 1.5 37.0 2470
1×120 5.5 2.0 1.5 38.8 2810
1×150 5.5 2.1 1.6 40.7 3245
1×185 5.5 2.2 1.6 42.9 3765
1×240 5.5 2.3 1.7 45.8 4510
1×300 5.5 2.4 1.8 48.5 5315
3×16 5.5 1.8 2.0 55.5 4950
3×25 5.5 1.9 2.0 62.2 5705
3×35 5.5 2.9 2.1 62.6 5990
3×50 5.5 3.0 2.2 65.4 6740
3×70 5.5 3.1 2.3 69.1 7790
3×95 5.5 3.3 2.4 73.0 9150
3×120 5.5 3.4 2.5 77.4 10580
3×150 5.5 3.6 2.6 81.9 12145
3×185 5.5 3.8 2.7 89.5 12265
3×240 5.5 4.0 2.9 96.1 14725
3×300 5.5 4.2 3.0 101.9 17190