Loading...

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables

Home/NEK 606 Offshore & Marine Cables/P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables Applications

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables are flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables Standards

IEC 60092-353IEC 60092-351
IEC 60092-359IEC 60332-1
IEC 60332-3-22IEC 60754-1,2
IEC 61034-1,2NEK 606:2004
P2 or P2/P9 RFOU/TFOU 3.6/6KVP2 or P2/P9 RFOU/TFOU 3.6/6KV

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables Construction

  • Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
  • Conductor Screen : Semi conducting material.
  • Insulation : Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
  • Insulation Screen : Semi conducting material and tinned copper wire braid.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath : Halogen free thermosetting compound, SHF2 (for TYPE P2), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P2/P9),coloured red.

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables Electrical Characteristics

Nominal Cross Section Areamm²162535507095120
Nominal Conductor Diametermm5.16.57.48.710.312.213.8
Maximum DC Resistant@20℃Ω/km1.160.7340.5290.3910.270.1950.154
Continuous Current Rating@45℃1 CoreA96127157196242293339
Continuous Current Rating@45℃3 CoreA6789110137169205237
Short Circuit Current 1sA2290358050107150100201359017170
Operating VoltageKV3.6/63.6/63.6/63.6/63.6/63.6/63.6/6

 

Nominal Cross Section Areamm²150185240300400500630
Nominal Conductor Diametermm15.117.019.621.924.627.632.5
Maximum DC Resistant@20℃Ω/km0.1260.10.07620.06070.04750.03690.0286
Continuous Current Rating@45℃1 CoreA389444522601690780890
Continuous Current Rating@45℃3 CoreA272311365421483546623
Short Circuit Current 1sA21460264703434042930572307154090140
Operating VoltageKV3.6/63.6/63.6/63.6/63.6/63.6/63.6/6

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors35404550556065707580
Rating Factor1.11.051.00.940.880.820.740.670.580.47

Mechanical and Thermal Properties

Bending Radius :15×OD (during installation); 9×OD (fixed installed).
Temperature Range : -20℃ ~ +90℃.

P2 or P2/P9 RFOU/TFOU 3.6/6KV Cables Dimensions and Weight

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Sheath Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
InnerOuter
1×162.51.41.122.8780
1×252.51.51.124.01020
1×352.51.51.225.11155
1×502.51.61.226.31320
1×702.51.61.328.21595
1×952.51.71.330.01905
1×1202.51.81.431.82235
1×1502.51.81.433.52550
1×1852.51.91.535.43015
1×2402.62.01.538.83725
1×3002.82.11.642.34625
1×4003.02.21.746.65420
1×5003.22.41.850.86610
1×6303.22.51.955.18170
3×162.52.21.644.92930
3×252.52.31.745.43390
3×352.52.41.847.63820
3×502.52.51.950.94495
3×702.52.72.054.85585
3×952.52.82.158.96765
3×1202.53.02.263.58165
3×1502.53.12.367.49495
3×1852.53.32.475.810660
3×2402.63.52.582.311660
3×3002.83.82.789.312940