Loading...

P34 BFOU-HCF 0.6/1 kV Cables

Home/NEK 606 Offshore & Marine Cables/P34 BFOU-HCF 0.6/1 kV Cables

P34 BFOU-HCF 0.6/1 kV Cables Applications

P34 BFOU-HCF 0.6/1 kV Cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.

P34 BFOU-HCF 0.6/1 kV Cables Standards

IEC 60092-353IEC 60092-351
IEC 60092-359IEC 60332-1
IEC 60332-3-22IEC 60754-1,2
IEC 61034-1,2NEK 606:2004
P34 BFOU-HCF 0.6/1 kVP34 BFOU-HCF 0.6/1 kV

P34 BFOU-HCF 0.6/1 kV Cables Construction

  • Conductors : Tinned annealed stranded compacted copper to IEC 60228 class 2.
  • Insulation : Mica tape + Halogen free EPR/XLPE.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath1 : Halogen free thermosetting compound, SHF2.
  • HC-fire protection : Extruded thermoplastic fire protection compound.
  • Taping : Lapped glass fibre tape.
  • Outer Sheath2 : Flame retardant halogen-free thermoplastic compound, SHF1, coloured black.

P34 BFOU-HCF 0.6/1 kV Cables Electrical Characteristics

Nominal Cross Section Areamm²1.52.5461635
Nominal Conductor Diametermm1.62.12.63.25.17.4
Maximum DC Resistant@20℃Ω/km12.27.564.73.111.160.529
Continuous Current Rating@45℃1 CoreA2330405296157
Continuous Current Rating@45℃2 CoreA2026344482133
Continuous Current Rating@45℃3&4 CoreA1621283667110
Short Circuit Current 1sA21036057086022905010
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/1

 

Nominal Cross Section Areamm²507095120150185240300
Nominal Conductor Diametermm8.710.312.213.815.117.019.621.9
Maximum DC Resistant@20℃Ω/km0.3910.270.1950.1540.1260.10.07620.0607
Continuous Current Rating@45℃1 CoreA196242293339389444522601
Continuous Current Rating@45℃2 CoreA167206249288331444444511
Continuous Current Rating@45℃3&4 CoreA137169205237272311365421
Short Circuit Current 1sA715010020135901717021460264703434042930
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/1

Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ ³√ N ), I1= Current rating for 1-core, N = Number of cores.

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors35404550556065707580
Rating Factor1.11.051.00.940.880.820.740.670.580.47

Mechanical and Thermal Properties

  • Bending Radius :20×OD (during installation); 12×OD (fixed installed).
  • Temperature Range : -20℃ ~ +90℃.

P34 BFOU-HCF 0.6/1 kV Cables Dimensions and Weight

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Diameter Over Bedding
mm
Nominal Diameter Over Sheath1
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
1×501.415.018.545.52900
1×701.416.520.547.53300
1×951.618.523.050.53800
1×1201.620.525.052.54260
1×1501.823.027.054.54750
1×1852.025.029.557.55380
1×2402.228.032.566.07050
1×3002.430.535.568.08000
2×1.51.010.013.040.51890
2×2.51.011.014.542.02080
3×1.51.010.514.042.02140
3×2.51.011.515.042.52200
3×41.013.016.543.02400
3×61.014.018.045.02600
3×161.018.523.050.03500
3×351.225.029.557.54840
3×701.433.039.072.08150
3×1201.641.048.081.511300
3×1501.846.054.588.513300
4×2.51.012.516.544.02300
4×61.015.519.547.52870
4×161.020.525.053.53830
7×1.51.014.017.544.52550
12×1.51.018.522.550.03140
27×1.51.026.531.064.55070
7×2.51.015.019.046.02760
12×2.51.020.524.552.03500