UKOOA Instrumentation Cable

UKOOA TYPE FM / TYPE FP 150/250V Fire Resistant Cable Application

These cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

UKOOA TYPE FM / TYPE FP 150/250V Fire Resistant Cable Standards

BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2

UKOOA TYPE FM / TYPE FP 150/250V Fire Resistant Cable Construction

ConductorsStranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Fire ProtectionMica glass tape
InsulationEPR complying with BS7655 GP4
Drain WireTinned copper drain wire
Individual ScreenAluminium mylar tape screen
BeddingCSP – SW2 compound complying with BS 7655
ArmourGalvanised steel wire braid to BS 6883
Outer SheathCSP – SW2 compound complying with BS 7655 (TYPE FM: Blue; TYPE FP: Grey).

 

UKOOA TYPE FM / TYPE FP 150/250V Fire Resistant Cable Dimensions and Weight

Construction
No. of cores×Cross section(mm²)
Nominal Insulation Thickness
mm
Nominal Thickness of Inner Sheath
mm
Nominal Thickness of Outer Sheath
mm
Mominal Overall Diameter
mm
Approx. Weight
kg/km
3×2×0.750.81.21.418.6580
7×2×0.750.81.41.623.2915
12×2×0.750.81.61.829.71420
20×2×0.750.82.12.740.12905
3×3×0.750.81.31.520.4700
7×3×0.750.81.51.726.61180
12×3×0.750.81.92.238.52550
1×4×0.750.81.21.314.6360
1×2×1.00.81.01.213.0295
1×3×1.00.81.01.213.6330
1×4×1.00.81.01.315.9380
3×2×1.50.81.31.421.6732
7×2×1.50.81.41.627.81242
12×2×1.50.81.71.936.42039
3×3×1.50.81.31.524.5780
7×3×1.50.81.51.732.11409
12×3×1.50.81.82.043.92301