Loading...

UKOOA Type XD 600/1000V Fire Resistant Cable

Home/UKOOA Offshore & Marine cables/UKOOA Type XD 600/1000V Fire Resistant Cable

UKOOA LV Power Cable

UKOOA Type XD 600/1000V Fire Resistant Cable Application

These cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

UKOOA Type XD 600/1000V Fire Resistant Cable Standards

BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2

UKOOA Type XD 600/1000V Fire Resistant Cable Construction

ConductorsStranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Fire ProtectionMica glass tape
InsulationEPR complying with BS7655 GP4
BeddingCSP – SW2 compound complying with BS 7655.
ArmourGalvanised steel wire braid to BS 6883
Outer SheathCSP – SW2 compound complying with BS 7655

 

UKOOA Type XD 600/1000V Fire Resistant Cable Dimensions and Weight

Construction
No. of cores×Cross section(mm²)
Nominal Insulation Thickness
mm
Nominal Thickness of Inner Sheath
mm
Nominal Thickness of Outer Sheath
mm
Nominal Overall Diameter
mm
Approx. Weight
kg/km
2×1.50.81.11.214.9270
2×2.50.81.11.215.7310
2×41.01.21.318.1430
2×61.01.21.419.3520
2×101.01.31.421.7680
2×161.01.41.524.2850
2×251.21.41.528.91500
2×351.21.61.831.11810
2×501.41.61.835.92510
2×701.41.61.840.23230
2×951.61.61.845.54220
2×1201.61.61.849.65125
2×1501.81.61.854.16210
2×1852.01.61.859.27500
2×2402.21.61.866.99440
2×3002.41.61.873.511500
3×1.50.81.11.215.9290
3×2.50.81.11.317.1390
3×41.01.21.319.3520
3×61.01.21.420.8620
3×101.01.31.523.4850
3×161.01.41.626.01150
3×251.21.61.831.31600
3×351.21.71.934.62200
3×501.41.82.038.53000
3×701.42.02.243.43980
3×951.62.22.448.95295
3×1201.62.22.453.56490
3×1501.82.22.458.57690
3×1852.02.22.464.49550
3×2402.22.22.466.712400
3×3002.42.22.479.214900
4×1.50.81.11.316.3360
4×2.50.81.11.317.3470
4×41.01.21.420.0620
4×61.01.31.521.8760
4×101.01.31.524.51100
4×161.01.31.527.51500
4×251.21.31.534.12100
4×351.21.82.037.02700
4×501.41.82.042.53400
4×701.42.12.448.14600
4×951.62.32.654.35700
4×1201.62.32.659.46900
4×1501.82.32.665.18200
4×1852.02.32.671.410260
4×2402.22.32.680.113200
4×3002.42.32.688.316300
5×1.50.81.11.317.3420
5×2.50.81.11.318.6550
5×41.01.11.322.0720
7×1.50.81.21.318.6520
7×2.50.81.21.420.3600
12×1.50.81.31.523.2850
12×2.50.81.41.625.6950
19×1.50.81.41.628.11100
19×2.50.81.51.730.81400
27×1.50.81.51.733.21500
27×2.50.81.71.936.71800
37×1.50.81.71.936.72700
37×2.50.81.71.940.82950
For the best cable price, please feel free to leave your requirement, We will reply to you in 12 hours.
Thank you for your message. We will contact you within 6 hours!
There was an error trying to send your message. Please try again later.

MRE-M2X(St)H 150/250V Mica Tape + XLPE Insulated, LSOH (SHF1) Sheathed, Overall Screened Fire Resistant Instrumentation & Control Cables(Multipair/Multitriple)

Go to Top