UKOOA LV Power Cable
UKOOA Type YC 600/1000V Fire Resistant Cable Application
These cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.
UKOOA Type YC 600/1000V Fire Resistant Cable Standards
BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2
UKOOA Type YC 600/1000V Fire Resistant Cable Construction
Conductors | Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228. |
Fire Protection | Mica glass tape |
Insulation | EPR complying with BS7655 GP4 |
Bedding | EVA – SW4 compound complying with BS 7655. |
Armour | Tinned Phosphor Bronze Wire Braid to BS2873-PB102 (now BS EN 12166) |
Outer Sheath | EVA – SW4 compound complying with BS 7655 |
UKOOA Type YC 600/1000V Fire Resistant Cable Dimensions and Weight
Construction No. of cores×Cross section(mm²) | Nominal Insulation Thickness mm | Nominal Thickness of Inner Sheath mm | Nominal Thickness of Outer Sheath mm | Nominal Overall Diameter mm | Approx. Weight kg/km |
1×1.0 | 0.8 | 1.1 | 1.2 | 10.0 | 158 |
1×1.5 | 0.8 | 1.1 | 1.2 | 10.3 | 179 |
1×2.5 | 0.8 | 1.1 | 1.2 | 10.7 | 200 |
1×4 | 1.0 | 1.1 | 1.2 | 11.8 | 273 |
1×6 | 1.0 | 1.1 | 1.2 | 12.3 | 357 |
1×10 | 1.0 | 1.1 | 1.2 | 13.5 | 410 |
1×16 | 1.0 | 1.1 | 1.2 | 14.7 | 504 |
1×25 | 1.2 | 1.1 | 1.2 | 17.3 | 593 |
1×35 | 1.2 | 1.1 | 1.3 | 18.4 | 777 |
1×50 | 1.4 | 1.1 | 1.4 | 20.2 | 987 |
1×70 | 1.4 | 1.1 | 1.4 | 22.4 | 1333 |
1×95 | 1.6 | 1.1 | 1.5 | 25.0 | 1575 |
1×120 | 1.6 | 1.2 | 1.6 | 27.1 | 1838 |
1×150 | 1.8 | 1.2 | 1.6 | 29.5 | 2310 |
1×185 | 2.0 | 1.2 | 1.7 | 33.1 | 2835 |
1×240 | 2.2 | 1.2 | 1.8 | 36.5 | 3570 |
1×300 | 2.4 | 1.2 | 1.9 | 40.0 | 4410 |
1×400 | 2.6 | 1.2 | 1.9 | 44.2 | 5985 |
1×500 | 2.8 | 1.2 | 1.9 | 48.6 | 7560 |
1×630 | 2.8 | 1.2 | 1.9 | 52.8 | 9282 |