Loading...

XLPE Insulated AC Medium-voltage Submarine Cable With Fibre Optic Cable

Home/Submarine Cables/XLPE Insulated AC Medium-voltage Submarine Cable With Fibre Optic Cable

XLPE Insulated AC Medium-voltage Submarine Cable With Fibre Optic Cable

Applications

These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and lakes. Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according to customers design and standards.

Construction

Submarine Cables

  • Conductor:Copper conductor, circular stranded compacted, water blocked.
  • Conductor Screening: Extruded semi-conductive compound.
  • Insulation: XLPE.
  • Insulation Screening: Extruded semi-conductive compound.
  • Screen: Copper wires and copper helix, swelling powder.
  • Laminated Core Sheath: Aluminium tape bonded to overlaying PE sheath
  • Fillers: Polypropylene filler.
  • Fibre-optic Element: Fibre optic cable.
  • Separator: Binder tapes.
  • Bedding Layer: Polypropylene strings.
  • Armour: Galvanized steel wires.
  • Serving: Hessian tapes, bituminous compound, polypropylene strings.

Electrical Data:

6/10(12) kV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.230.43167
500.260.41199
700.290.38241
950.320.37288
1200.350.35327
1500.380.34363
1850.420.33405
2400.470.32464

12/20(24) kV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
350.170.47171
500.180.44199
700.200.41243
950.220.40292
1200.240.38328
1500.260.37364
1850.280.35408
2400.310.34467

18/30(36) kV

Nominal Cross Section AreaCapacitanceInductanceCurrent Rating
mm²μF/mmmH/kmA
500.140.48202
700.150.45245
950.170.42291
1200.180.41330
1500.190.39366
1850.210.38411
2400.230.36470

Dimension and Weight:

6/10(12) kV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal
Screen Cross Section Area
Nominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing
Thickness
Overall
Diameter
Weight
mm²mmmmmm²mmmmmmmmmmmmkg/m
357.03.4162.52423.153.5707.5
508.23.4162.52523.153.5738.2
709.93.4162.52724.03.5779.9
9511.53.4162.52824.03.58011.1
12013.03.4162.53024.03.58412.2
15014.53.4252.53124.03.58713.6
18516.13.4252.53325.04.09316.8
24018.63.4252.53525.04.09919.1

12/20(24) kV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal
Screen Cross Section Area
Nominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing
Thickness
Overall
Diameter
  Weight
mm²mmmmmm²mmmmmmmmmmmmkg/m
357.05.5162.52823.153.5788.8
508.25.5162.53023.153.5839.3
709.95.5162.53124.03.58711.4
9511.55.5162.53324.03.58912.7
12013.05.5162.53424.04.09414.1
15014.55.5252.53624.04.09715.3
18516.15.5252.53725.04.010218.6
24018.65.5252.54025.04.010821.1

18/30(36) kV

Nominal Cross Section AreaNominal Conductor DiameterNominal Insulation ThicknessNominal
Screen Cross Section Area
Nominal Core Sheath ThicknessNominal Core DiameterNominal Bedding ThicknessNominal Steel Wire DiameterServing
Thickness
Overall
Diameter
Weight
mm²mmmmmm²mmmmmmmmmmmmkg/m
508.28.0162.53523.153.59311.1
709.98.0162.53624.04.09912.8
9511.58.0162.53824.04.010214.9
12013.08.0162.53924.04.010516.2
15014.58.0252.54124.04.010817.6
18516.18.0252.54225.04.011321.0
24018.68.0252.54525.04.011923.4
For the best cable price, please feel free to leave your requirement, We will reply to you in 12 hours.
Thank you for your message. We will contact you within 6 hours!
There was an error trying to send your message. Please try again later.

MRE-M2XH PiMF/TiMF 150/250V Mica Tape + XLPE Insulated,LSOH (SHF1) Sheathed, Individual Screened Fire Resistant Instrumentation & Control Cables Multipair/Multitriple)

MRE-2XH PiMF/TiMF 150/250V XLPE Insulated, LSOH (SHF1) Sheathed, Individual Screened Flame Retardant Instrumentation & Control Cables (Multipair/Multitriple)

Go to Top