Loading...

XLPE Insulated DC High-Voltage Submarine Cable

Home/Submarine Cables/XLPE Insulated DC High-Voltage Submarine Cable

XLPE Insulated DC High-Voltage Submarine Cable

Applications

These submarine cables are used for power transmission to offshore islands, oil platforms or to cross-rivers and lakes. Cable design based on the mayor national or international standards e.g. VDE, IEC and ICEA or according to customers design and standards .

Construction

Submarine Cables

  • Conductor:Copper conductor, water blocked.
  • Conductor Screening: Extruded semi-conductive compound.
  • Insulation: XLPE.
  • Insulation Screening: Extruded semi-conductive compound.
  • Separator: Swelling tape.
  • Core Sheath1: Lead Sheath.
  • Core Sheath2: PE sheath.
  • Bedding: Bedding layer.
  • Armour: Galvanized steel wires filled with bitumen compound.
  • Serving: Polypropylene yarn.

Electrical Data:

127/220(245) kV

Nominal
Cross Section Area
CapacitanceInductanceCharging Current per phase
@50Hz
mm²μF/kmmH/kmA/km
5000.141.425.8
6300.161.406.4
8000.171.376.9
10000.191.357.4
12000.201.337.8
14000.211.328.2
16000.221.318.6

160/275(300) kV

Nominal
Cross Section Area
CapacitanceInductanceCharging Current per phase
@50Hz
mm²μF/kmmH/kmA/km
5000.141.426.8
6300.161.407.7
8000.171.378.3
10000.181.359.0
12000.191.339.5
14000.201.3210.0
16000.211.3110.4

200/345(362) kV

Nominal
Cross Section Area
CapacitanceInductanceCharging Current per phase
@50Hz
mm²μF/kmmH/kmA/km
6300.141.408.8
8000.151.379.7
10000.171.3510.7
12000.181.3311.1
14000.191.3211.6
16000.201.3112.1

230/400(420) kV

Nominal
Cross Section Area
CapacitanceInductanceCharging Current per phase
@50Hz
mm²μF/kmmH/kmA/km
6300.131.409.6
8000.151.3710.7
10000.161.3511.7
12000.181.3312.9
14000.191.3213.5
16000.191.3114.1

Dimension and Weight:

127/220(245) kV

Nominal
Cross Section Area
Nominal
Conductor
Diameter
Nominal
Insulation
Thickness
Nominal
Diameter Over
Insulation
Nomanal
Lead Sheath
Thickness
Nominal Overall
Diameter
Weight
mm²mmmmmmmmmmkg/m
50026.224.077.62.9111.029.3
63029.823.079.23.0112.831.2
80033.723.083.13.1117.534.5
100037.923.087.33.1121.937.7
120041.223.090.63.1125.240.4
140044.423.093.83.1128.643.2
160047.423.096.83.1131.846.0

160/275(300) kV

Nominal
Cross Section Area
Nominal
Conductor
Diameter
Nominal
Insulation
Thickness
Nominal
Diameter Over
Insulation
Nomanal
Lead Sheath
Thickness
Nominal Overall
Diameter
Weight
mm²mmmmmmmmmmkg/m
50026.226.081.63.0115.231.1
63029.824.081.23.0114.831.8
80033.724.085.13.1119.535.2
100037.924.089.33.1123.938.4
120041.224.092.63.1127.441.6
140044.424.095.83.1130.644.4
160047.424.098.83.1133.847.2

200/345(362) kV

Nominal
Cross Section Area
Nominal
Conductor
Diameter
Nominal
Insulation
Thickness
Nominal
Diameter Over
Insulation
Nomanal
Lead Sheath
Thickness
Nominal Overall
Diameter
Weight
mm²mmmmmmmmmmkg/m
63029.828.089.23.1123.435.2
80033.727.091.13.1125.937.5
100037.926.093.33.1128.139.9
120041.225.094.63.1129.442.0
140044.425.097.83.1132.844.9
160047.425.0100.83.1135.847.7

230/400(420) kV

Nominal
Cross Section Area
Nominal
Conductor
Diameter
Nominal
Insulation
Thickness
Nominal
Diameter Over
Insulation
Nomanal
Lead Sheath
Thickness
Nominal Overall
Diameter
Weight
mm²mmmmmmmmmmkg/m
63029.832.098.23.1132.838.8
80033.730.098.13.1133.140.2
100037.929.0100.33.1135.342.6
120041.227.099.63.1134.644.0
140044.427.0102.83.1138.046.9
160047.427.0105.83.1141.049.7
For the best cable price, please feel free to leave your requirement, We will reply to you in 12 hours.
Thank you for your message. We will contact you within 6 hours!
There was an error trying to send your message. Please try again later.

MRE-M2XH PiMF/TiMF 150/250V Mica Tape + XLPE Insulated,LSOH (SHF1) Sheathed, Individual Screened Fire Resistant Instrumentation & Control Cables Multipair/Multitriple)

Go to Top